A relay is connected to a 400/5 current transformer. For a fault current of 2.4 kA and relay setting of 150%, the PSM is:

This question was previously asked in
SJVNL ET Electrical 2019 Official Paper
View all SJVN Executive Trainee Papers >
  1. 8
  2. 12
  3. 4
  4. 16

Answer (Detailed Solution Below)

Option 3 : 4
Free
SJVN ET General Awareness Mock Test
0.8 K Users
20 Questions 20 Marks 12 Mins

Detailed Solution

Download Solution PDF

Explanation:

Numerical Solution: Protective System Multiplier (PSM)

The given problem involves calculating the Protective System Multiplier (PSM) for a relay connected to a current transformer (CT) with a given fault current and relay setting percentage. Below is the detailed solution:

Step 1: Understanding Protective System Multiplier (PSM):

The Protective System Multiplier (PSM) is defined as the ratio of the fault current (secondary current of the CT during a fault) to the relay pickup current. It is mathematically expressed as:

PSM = (Fault Current in CT Secondary) ÷ (Relay Pickup Current)

Where:

  • Fault Current in CT Secondary: This is the current flowing through the secondary winding of the current transformer during a fault condition.
  • Relay Pickup Current: This is the threshold current at which the relay starts to operate. It is calculated using the relay setting percentage.

Step 2: Given Data:

  • Current Transformer Ratio: 400/5
  • Fault Current (Primary Side): 2.4 kA = 2400 A
  • Relay Setting: 150%

Step 3: Calculate Fault Current in CT Secondary:

The fault current in the secondary winding of the CT can be calculated using the CT ratio:

Fault Current in CT Secondary = (Fault Current in Primary Side × CT Secondary Rating) ÷ CT Primary Rating

Substituting the values:

Fault Current in CT Secondary = (2400 × 5) ÷ 400

Fault Current in CT Secondary = 30 A

Step 4: Calculate Relay Pickup Current:

The relay pickup current is determined using the relay setting percentage. Relay setting is given as 150%, which means:

Relay Pickup Current = (Relay Setting × CT Secondary Rating) ÷ 100

Substituting the values:

Relay Pickup Current = (150 × 5) ÷ 100

Relay Pickup Current = 7.5 A

Step 5: Calculate PSM:

Now, the PSM can be calculated using the formula:

PSM = (Fault Current in CT Secondary) ÷ (Relay Pickup Current)

Substituting the values:

PSM = 30 ÷ 7.5

PSM = 4

Step 6: Final Answer:

The Protective System Multiplier (PSM) is 4. Therefore, the correct answer is Option 3

Latest SJVN Executive Trainee Updates

Last updated on Jul 15, 2025

-> SJVN Executive Trainee Written Exam date is out, The computer based exam will be held on 10th, 14th August 2025.

->SJVN Executive Trainee recruitment 2025 application form has been released. Applicants can apply for the SJVN recruitment 2025 Executive Trainee till May 18.

->SJVN Limited has announced the recruitment notification for the position of Executive Trainee 2025.

->A total of 114 vacancies are available for the SJVN Executive Trainee Recruitment across various disciplines such as Civil, Mechanical, Electrical, Environment, Electronics & Communication, and more.

->The selection process of SJVN Executive Trainee recruitment 2025, as per the previous notification, includes a Computer-Based Test, Group Discussion, and Personal Interview.

->Once selected, candidates will be required to sign a service agreement bond of Rs. 10,00,000/- (Rs. 7,50,000/- for SC/ST/PWD candidates), committing to complete the prescribed training and serve the company for a minimum of 3 years.

->Candidates must refer to the SJVN Executive Trainee Previous Year Papers and boost their preparation for the exam.

Get Free Access Now
Hot Links: teen patti apk download teen patti yas teen patti master 2024 teen patti real cash withdrawal real cash teen patti